PEROXIDE-CROSS-LINKED COMPOUNDS XLPE

IPC-35

Insulation peroxide-crosslinked compound for medium voltage power cables (6-35 kV).
Description

Description: Insulation peroxide-crosslinked compound for medium voltage power cables (6-35 kV).

Application: Insulation for medium voltage power cables (6-35 kV).

TU 2243-003-63982493-2015

Technical Specifications:

Indicator* Value Requirements Method
Physical Density, g/cm³ 0.915 0.915-0.925 GOST IEC 60811
MFR, g/10 min (190 °C / 2.16 kg) 2.0 1.5 – 3.0 GOST IEC 60811
Tensile Strength, MPa, minimum 22.0 ≥15 GOST IEC 60811
- Elongation at Break, %, minimum 730.0 ≥300 GOST IEC 60811
Thermal Deformation - Relative Elongation, %, maximum 75 0 ≤100 ≤5 GOST IEC 60811
Change in Tensile Strength after Aging (168 hours at 135 °C), %, maximum: + 7.0 - 5.0 ±25 ±25 GOST IEC 60811
Specific Volume Resistance, Ohm cm 19*1015 >1015 GOST IEC 60811
Dielectric Permittivity (50 Hz) 2.3 <2.6 GOST IEC 60250 (IEC 62631-2-1:2018)
Dissipation Factor (50 Hz) 0.00043 <0.0005 GOST IEC 60250 (IEC 62631-2-1:2018)
Electrical Strength, kV/mm 28 >22 GOST IEC 60243
Moisture Content, % 0.03 <0.1 GOST IEC 26359
   

*Samples are produced by direct pressing from granules at a temperature of 165 °C in the press and a holding time of 15 minutes with intermediate pressing.

Processing Modes:

  • Extrusion Temperature Profile: 80 – 105 – 107 – 108 – 109 – 110 – 113 – 115 – 118 – 120 °C
  • Vulcanization Tube Temperature: 320 – 420 °C

Storage Conditions: It is recommended to store in a closed, dry room, avoiding direct sunlight at a temperature from 10 °C to 35 °C and humidity of 40-70%.

Shelf Life: 1 year from the production date.

Before processing, the material should be acclimatized in a warm room at a temperature of at least 10 °C for a minimum of 24 hours.

The material is packaged in corrugated octabins with a net weight of 750 kg (with a PE liner inside).